How to protect rooftop PV systems from fire risk

Dutch research institute TNO has released a series of guidelines to reduce fire hazards in rooftop PV installations. The study follows a series of fire accidents that occurred between 2018 and 2020 in the Netherlands, for which the main causes were identified.

From pv magazine Global. [2]

The Netherlands Organization for Applied Scientific Research (TNO)[3] and the Dutch Institute for Safety have published a guide to help homeowners or businesses operating a rooftop PV system, or willing to install one, become aware of the fire risks associated with solar power generation.

The guide also provides firefighters with tools to act quickly and safely in the event of an incident and defines the most common fire causes, such as bad system design, inadequate installation, animals chewing on wiresstorm damages, manufacturing faults in PV products, including connectors and junction boxes, and heat accumulation, among others.[4]

The basic principle proposed by the TNO experts is that a PV system, including the inverter, must have its own fire compartments, as far as this is possible. These compartments should comply with the Dutch WBDBO requirement, which establish that the fire in a building should be stopped in 30, 60, 90 or 120 minutes, depending on the type of building and its function. WBDBO stands for Weerstand tegen BrandDoorslag en BrandOverslag, which translates to Resistance Fire Bursts and Fire Spread.

For the layout of a commercial roof with solar panels, we recommend working with surfaces of a maximum of 40 by 40 meters, or 1,600 square meters, as in this way the firefighters can still reach all solar panels during their operation,” the Dutch experts said, adding that a safe space must be maintained between the PV system compartments, also in residential installations. “What is also very important if a fire breaks out is that the firefighters can find all information about the existing PV system in the meter cupboard or at the entrance of the building,” they explained. This should help the firefighters identify the location of the inverter, the possible presence of a storage system, and a fireman’s switch.

The guide is said to be a working paper that will be updated constantly according to adjustments in regulations and technology.

In September 2018, the Netherlands enterprise agency Rijksdienst voor Ondernemend Nederland (RVO) tasked the TNO to conduct an investigation into fire accidents involving rooftop PV systems reported by Dutch media at the time. In April 2019, the research institute ended its investigation and stated that around 70% of the fires were caused by faulty connectors[7], and especially by cross-mating, which happens when connectors of different kinds are mated.[5][6]

In December, Underwriters Laboratories[8], a U.S. nonprofit standards development organisation, published the new UL 3741 safety standard[9], which is related to the evaluation of PV hazard control functions.

This content is protected by copyright and may not be reused. If you want to cooperate with us and would like to reuse some of our content, please contact: editors@pv-magazine.com[10].

References

  1. ^ Posts by Emiliano Bellini (www.pv-magazine-australia.com)
  2. ^ From pv magazine Global.  (www.pv-magazine.com)
  3. ^ Netherlands Organization for Applied Scientific Research (TNO) (www.tno.nl)
  4. ^ guide (www.ifv.nl)
  5. ^ investigation into fire accidents (www.pv-magazine.com)
  6. ^ rooftop PV (www.pv-magazine.com)
  7. ^ 70% of the fires were caused by faulty connectors (www.pv-magazine.com)
  8. ^ Underwriters Laboratories (www.pv-magazine.com)
  9. ^ UL 3741 safety standard (www.pv-magazine.com)
  10. ^ editors@pv-magazine.com (www.pv-magazine-australia.com)

Click here to read original article

Leave A Reply

This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you wish. Accept Read More